# 1 FAQ = High Water in Brine Tank - Problem -Softener does not remove the water from my salt tank or overflow 1. Make sure all the fittings are tight. Also check the tubing going to the salt tank for small cracks. Any air leak will cause the valve to not draw the water out during the regeneration cycle.
|
# 1 FAQ = High Water in Brine Tank - Problem -Softener does not remove the water from my salt tank or overflow 1. Make sure all the fittings are tight. Also check the tubing going to the salt tank for small cracks. Any air leak will cause the valve to not draw the water out during the regeneration cycle.
|
# 1 FAQ = High Water in Brine Tank - Problem -Softener does not remove the water from my salt tank or overflow 1. Make sure all the fittings are tight. Also check the tubing going to the salt tank for small cracks. Any air leak will cause the valve to not draw the water out during the regeneration cycle.
|
# 1 FAQ = High Water in Brine Tank - Problem -Softener does not remove the water from my salt tank or overflow 1. Make sure all the fittings are tight. Also check the tubing going to the salt tank for small cracks. Any air leak will cause the valve to not draw the water out during the regeneration cycle.
|
# 1 FAQ = High Water in Brine Tank - Problem -Softener does not remove the water from my salt tank or overflow 1. Make sure all the fittings are tight. Also check the tubing going to the salt tank for small cracks. Any air leak will cause the valve to not draw the water out during the regeneration cycle.
|
# 1 FAQ = High Water in Brine Tank - Problem -Softener does not remove the water from my salt tank or overflow 1. Make sure all the fittings are tight. Also check the tubing going to the salt tank for small cracks. Any air leak will cause the valve to not draw the water out during the regeneration cycle.
|
5600 - difference between metered demand control and 12 day valve What is the difference between metered demand control and 12 day skipper wheel?
* Metered..
Meter Demand Operation
** The Fleck 5600 version - 12 day works ( regenerates ) according to the " |
5600 - difference between metered demand control and 12 day valve What is the difference between metered demand control and 12 day skipper wheel?
* Metered..
Meter Demand Operation
** The Fleck 5600 version - 12 day works ( regenerates ) according to the " |
5600 - Manual Regenerate - Cycle Times To regenerate the Fleck 5600 valve used on softener, without working timer motor.
The following steps are involved in regeneration: Time to leave in each cycle
Regen - none, valve does nothing |
5600 - Manual Regenerate - Cycle Times To regenerate the Fleck 5600 valve used on softener, without working timer motor.
The following steps are involved in regeneration: Time to leave in each cycle
Regen - none, valve does nothing |
Adapt New Valve to Smaller Pipe in Tank Question: New Valve Body has 1.05" distributor pipe opening, and my old center distributor pipe ( or "riser pipe" ) is only 13/16" O.D.. What do I do next?
* 3 ways to "Adapt" valve body to 13/16" |
Aerator Use and Cleaning Q & A Hydrogen sulfide is a gas that causes an obnoxious rotten egg odor in your water. Most noticeable when water is first turned on ( because the gas separates from the water and collects in the pipes as |
Air Check - Ball seated or dropping early during the BRINE/SLOW RINSE portion on the 155 or 255 Series Valve Can you clarify whether the air check should be seated or not during the BRINE/SLOW RINSE portion of operation?
** ONLY after sucking out the water from the salt tank, THEN it drops and "seats" t |
Air Check - Ball seated or dropping early during the BRINE/SLOW RINSE portion on the 155 or 255 Series Valve Can you clarify whether the air check should be seated or not during the BRINE/SLOW RINSE portion of operation?
** ONLY after sucking out the water from the salt tank, THEN it drops and "seats" t |
Air Check - Ball seated or dropping early during the BRINE/SLOW RINSE portion on the 155 or 255 Series Valve Can you clarify whether the air check should be seated or not during the BRINE/SLOW RINSE portion of operation?
** ONLY after sucking out the water from the salt tank, THEN it drops and "seats" t |
Air Check inside Brine Tank can becomes Stuck or Water Logged The Problem as related by Customer:
When checking the brine tank valve assembly--even though I already took it apart and cleaned it--I also replaced all brine tubing. When I took out the brine tank |
Air in water lines after Softener Regenerates If you notice AIR in the water lines the morning after your softener has regenerated, AND the brine water level is normal ( meaning the valve has been sucking the water out and refilling properly ), t |
Autotrol 155 or 255 - How to Tell Which You Have How do I know if I have an Autotrol 155 ( 1550-TC ) or a model 255 Valve?
The Series 155 was replaced by the Series 255 late 1995 ( early 1996 ). An easy way to tell the difference is, the |
Autotrol Date Codes - Serial Numbers How do I know when my Autotrol 150, 160, 155 ( 1550-TC ), 163, 168, 255, 263, or a model 268 Valve was made?
Example of Newer Models
The serial number is: 255189030016
This is found on a |
Average Salt Amount Needed and Normal Water Level In Brine Tank The amount of salt needed to properly recharge a water softener is mostly based on the amount of resins being recharged. 3/4 cu.ft. resin = 6 - 9 lbs. 1 cu.ft. resin = 8 - 10 lbs. 1.5 cu.ft resin = 1 |